Blower door test, explained in plain numbers.
How the test works, how the result is calculated, and what the number means for a Houston home.

What the fan is doing.
A calibrated fan mounted in an exterior door pulls air out of the house until the inside is 50 pascals lower than outside. Air rushes in through every crack to replace it. The fan flow needed to hold 50 pascals is CFM50, the leakage of the whole house.
From CFM50 to ACH50.
Formula in words: ACH50 equals CFM50 times 60, divided by the house volume in cubic feet.
Step 1, volume. 1,800 square feet × 8.5-foot average ceiling = 15,300 cubic feet.
Step 2, measure. The fan reads 1,530 CFM50.
Step 3, hourly. 1,530 × 60 = 91,800 cubic feet per hour.
Step 4, divide. 91,800 ÷ 15,300 = 6.0 ACH50.
Meaning. The house exchanges its air volume six times an hour at test pressure. New Houston homes must meet 5.0 or less under the 2021 IECC; an existing home at 6.0 is fairly typical and has room for air sealing.
Rough ranges for Houston homes.
| ACH50 | What it usually means |
|---|---|
| Above 10 | Leaky; big savings and comfort gains from air sealing |
| 6 to 10 | Average for older existing homes |
| 3 to 5 | Meets current code for new construction in Climate Zone 2 |
| Below 3 | Tight; mechanical ventilation planning is important |
Ranges are general guidance from field experience, not code values. The 5.0 limit is from the 2021 IECC.
Rated 4.9 on Google.
Real reviews from Houston homeowners and property owners. Read every review on Google or see more on our reviews page.
“Needed a plumber for a water leak emergency. Keith and his crew were here within 45 mins from calling. They met with the adjuster and had our home back to perfect within 2 months.”— Alex A., Yahoo Local review
“Keith is the owner, he is friendly, professional. Very detail-oriented. He makes sure everything is done correctly.”— Pam G., Angi review
“Very impressed by Keith’s skills and experience. He was able to identify and fix my plumbing issues, and was very honest about what needed to be fixed now, and what could wait.”— Thor Oxnard, Google review
One call. Every trade. Any hour.
Plumbing, HVAC, water, fire, mold and building diagnostics — handled by one licensed Houston team since 2013.
Frequently asked.
Still unsure? Call (832) 904-9001 and talk to a licensed professional — not a call center.
Why does volume matter?
Does a blower door test find leaks?
Code, standard and agency references used on this page. Requirements change; confirm the edition your jurisdiction or carrier applies.
- 2021 IECC Residential, Chapter 4 (air leakage testing, R402.4)
- Town of Prosper, TX: 2021 IECC Residential Testing Compliance Template
- TDLR Technical Bulletin IHB TB 12-02: Blower door test procedure conditions
- City of Houston Ordinance 2023-907 adopting the 2021 IECC with amendments (effective Jan. 1, 2024)